NuTone Vacuum Cleaner CV352 User Manual

BUILT-IN CENTRAL  
CLEANING SYSTEM  
MODEL: CV-352  
GENERAL INFORMATION..............2  
Power Unit Installation ....................7  
Dimensional Chart ........................7  
Mounting .......................................7  
Tubing connections.......................7  
Wiring............................................7  
LAYOUT AND PLANNING...............2  
Examples ........................................2  
Locating the Power Unit..................3  
Locating the Wall Inlets...................3  
Tubing.............................................3  
INSTALLATION IN  
EXISTING CONSTRUCTION ...........8  
Layout and Planning .......................8  
Locating Access Keys.....................8  
Wall Inlet Installation.......................8  
Model 330 Wall Inlet ...................10  
INSTALLATION IN  
NEW CONSTRUCTION....................4  
Wall Inlet Rough-In .........................4  
Installing the Tubing........................4  
Installation Hints............................4  
Tubing Installation.........................5  
Wall Inlet Installation.......................6  
Model 360 Wall Inlet .....................6  
Model 330 Wall Inlet .....................6  
FLOOR INLET INSTALLATION.....10  
FINAL SYSTEM CHECK................11  
 
BRANCH  
LINES  
THE SPLIT-LEVEL HOUSE  
VERTICAL  
BRANCH  
LINE  
Like the two-story house, the split level installation  
commonly calls for a two-level trunk line.  
TRUNK  
LINE  
Here, the power unit is  
EXHAUST  
located in the garage.  
The intake tubing runs  
exposed up the  
garage wall and  
into the ground level  
section's attic.  
Two branch lines  
connect this part  
of the trunk line to inlet  
lines which  
INLET  
LINE  
INTAKE  
INLET  
POWER  
UNIT  
BRANCH  
LINE  
INLET  
are dropped  
inside interior walls. A vertical  
branch line runs to the upstairs attic,  
where the trunk line  
FIGURE 3  
branches into a T-shape.  
This trunk line connects to two  
upstairs inlet lines and to one inlet line which drops through an  
upstairs wall and down into  
the third-level utility room. This last inlet services  
both the utility room and a large L-shaped recreation room.  
See Figure 3.  
LOCATING THE POWER UNIT  
• Locate the power unit away from the general living area.  
• The power unit is equipped with an inlet. When planning,  
remember the power unit has an inlet for a garage, basement,  
utility room, etc.  
• If the power unit is located in a closet or a small utility room,  
make sure the area is well-ventilated (i.e., with door louvers).  
• The power unit should be exhausted to the outside. The  
exhaust should not be vented into a wall, a ceiling or a  
concealed space in the house. The exhaust line should be  
terminated outside the home, using Model 393 Wall Cap or a  
roof vent.  
• Locate the power unit in an accessible area for changing the  
soil bag and periodically cleaning the secondary filter.  
• Locate the power unit within six feet of a grounded electrical  
outlet. The power unit requires a 120 vAC power source.  
• Do not locate the power unit close to a source of extreme heat  
(i.e., water heater) or in an area with an ambient high  
temperature (i.e., attic, furnace room).  
WARNING  
Power unit must not be mounted in a high ambient  
temperature area such as attic, furnace room, etc.  
LOCATING THE WALL INLETS  
• Locate inlets on interior walls.  
• Locate inlet within six feet of an electrical outlet to allow use of  
optional current-carrying hose.  
• Be sure tubing will not obstruct electrical, plumbing or other  
mechanical installation.  
• Choose central locations which allow several rooms to be  
cleaned from a single inlet.  
• Locate inlets centrally so that a maximum area can be cleaned  
with the 30' hose.  
• Be sure inlets will not be blocked by doors or furniture.  
TUBING  
• The installation should consist of a main trunk line running from  
the farthest wall inlet to the power unit location, with branch  
lines running to each additional inlet. Beginning at the area  
farthest from the power unit, choose a tentative inlet location.  
measure (30 feet for 30 foot hose) from the proposed inlet  
location to the farthest corner of the rooms to be cleaned by  
that inlet to determine if inlet location is proper.  
procedure to determine each additional inlet location, always  
working toward the power unit.  
• Generally, an installation will require 3 to 4 inlets and 16 to 20  
feet of tubing per inlet. It is suggested that a floor plan be used  
to more accurately determine the quantity of materials needed.  
NOTE: Conventional metal or plastic strapping should  
support the exhaust tubing when a muffler is used, or at the  
joints of long runs of tubing where another means of  
support is not available.  
• Move tentative inlet location if necessary. Use the same  
3
 
INSTALLATION IN NEW CONSTRUCTION  
WALL INLET ROUGH-IN  
1. Once the locations for wall inlets have been determined,  
mount all inlet brackets.  
2. To locate bracket on wall stud, measure approximately 18" up  
from finished floor level. (Height may vary according to  
individual preference.)  
MODEL 361  
3. Refer to Figure 4. Model 361 for using 360 inlet. Nail bracket  
MODEL 329  
SIDE  
MOUNTING  
FACE  
MOUNTING  
to side of stud so that front edge of bracket is flush to front of  
stud. (The bracket may also be nailed to the front edge of the  
stud. For front stud mounting, use locating tabs on bracket for  
proper alignment.)  
4. Refer to Figure 5. Model 329 for use with 330 inlets. Remove  
cardboard from plaster guard frame. Using four (4) provided  
screws, attach the appropriate flanged fitting and inlet seal to  
back of inlet.  
5. Replace cardboard in plaster guard frame.  
6. When using Model 329 glue elbow to mounting plate.  
NOTE: Configuration of spacer may vary depending upon  
installation.  
NOTE: When using the Model 361 inlet bracket on walls  
thinner than 12", use a 14" spacer (not furnished) between  
the wall and the inlet bracket. See Figure 5A.  
Spacer may be made from plywood, masonite, etc. Contact  
cement may be used to hold spacer in place during assembly.  
23/8"  
113/16"  
FIGURE 4  
SPACER  
1/4"  
WALL LESS THAN  
1/2" THICK.  
INLET MOUNTING  
BRACKET  
31/4"  
PLASTER  
GUARD  
HOLE  
21/4"  
FIGURE 5A  
FIGURE 5  
INSTALLING THE TUBING  
INSTALLATION HINTS  
MODEL 361 MOUNTING  
Use the following installation guidelines when installing the  
tubing.  
21/2" DIA. HOLE  
THROUGH SOLE PLATE  
1. Start tubing installation at farthest inlet and work toward the  
power unit.  
23/8"  
113/16"  
2. Tubing run to the power unit should be as straight as  
possible.  
113/16"  
113/16"  
3. When assembling sections with elbows and tees, make sure  
the curve in the fitting is aligned so that the air flows toward  
the power unit.  
4. Branch lines should always join the trunk line from above or  
from the same level. Never join a branch line from an angle  
below the trunk line.  
SIDE  
MOUNTING  
FACE  
MOUNTING  
MODEL 329 MOUNTING  
21/2" DIA. HOLE  
THROUGH SOLE PLATE  
2"  
5. Secure tubing to joists or studs.  
2"-382s  
2 / -382  
6. Refer to Figure 20 on page 7. Run low voltage wiring and  
secure wiring to tubing. Leave approximately 6" of wire for  
connection to each inlet.  
5
8
FACE  
MOUNTING  
FIGURE 6  
4
 
TUBING INSTALLATION  
INCLUDE FITTING  
RECESS IN  
1. Cut a 212" diameter hole in sole plate, header or stud directly  
in line with opening of inlet bracket fitting. Note Figures 6  
and 4 for center line dimensions.  
MEASUREMENT  
3/4"  
3/4"  
TUBING MEASUREMENT  
PVC TUBING  
2. Refer to Figure 7. Measure length of tubing needed to  
connect inlet to trunk line. Allow approximately 34" of tubing  
for inserting into fittings.  
FITTING  
FITTING  
FIGURE 7  
3. Refer to Figure 8. Cut tubing, keeping cut square.  
4. Refer to Figure 9. Remove burrs from both inside and  
outside of tubing.  
5. Before cementing, pre-assemble section to inlet fitting, check  
for proper length.  
6. Refer to Figure 10. Apply cement (Model 379) to outside of  
tubing. Coat tubing approximately 1" back. Take care to keep  
cement from inside of tube.  
7. Refer to Figure 11. Insert tubing into fitting with a twisting  
motion to evenly spread cement. Be sure tubing is firmly  
seated in fitting.  
8. If fittings have been attached to tubing at the end opposite the  
inlet bracket, be sure alignment is proper before cement sets.  
9. Refer to Figure 12. Low voltage wiring (Model 376) should  
be completed as tubing is installed. Tape wire to tubing to  
hold in place and insert through hole in inlet bracket.  
FIGURE 8  
FIGURE 9  
NAIL PLATE INSTALLATION  
Caution: When tubing is run through the wall stud, sole  
plate, headers - or anywhere that building materials will be  
attached - place a nail plate (Model 378) over that area  
(on both sides if necessary) to prevent nails from piercing  
tubing.  
FIGURE 10  
FIGURE 11  
FIGURE 12  
5
 
WALL INLET INSTALLATION  
MODEL 360 WALL INLET(361 Rough in)  
1. Once the walls have been finished, install the wall inlets.  
2. Remove the cardboard plaster guard.  
3. Refer to Figure 13. For some dry wall or panel construction,  
the plaster frame will extend beyond the finished wall. In this  
case, remove plaster frame from mounting bracket by  
removing mounting screws.  
4. Refer to Figure 14. Connect 2-conductor low voltage wire to  
terminal screws on back of wall inlet.  
FIGURE 13  
FIGURE 14  
5. Guide excess wire back through hole in inlet bracket and  
make sure seal is secure between mounting bracket and  
flanged fitting.  
6. Refer to Figure 15. Place inlet into mounting bracket and  
secure.  
NOTE: When wall inlets are installed in 1/2" thick walls or  
less, the tube of the wall inlet may extend into elbow area of  
the flanged fitting and cause blockage. Shorten the wall  
inlet tube to prevent this condition. See Figure 16.  
For extra thick walls, use Model 399 extension sleeves to  
connect inlet to the flanged fitting.  
FIGURE 15  
MODEL 330 WALL INLET (329 Rough in)  
See Figure 17.  
1. Connect 2-conductor low voltage wire to terminal screws on  
back of wall inlet.  
MODEL 365  
DOUBLE FLANGED  
TEE  
WALL  
INLET  
2. Align inlet mounting holes with holes in mounting plate.  
3. Place inlet into mounting plate and secure with two provided  
screws.  
SHORTEN  
MOUNTING  
BRACKET  
WALL  
FIGURE 16  
INLET  
MOUNTING  
PLATE  
FIGURE 17  
6
 
POWER UNIT INSTALLATION  
MINIMUM WALL CLEARANCE DIMENSIONS  
12"  
MOUNTING See Figure 18.  
18"  
1. Locate the power unit within six feet of a grounded electrical  
outlet.  
2. Drill 316" diameter pilot holes for the two (2) mounting screws in a  
wall stud or strong support. See Figure 19.  
EXHAUST  
3. Tighten mounting screws. Leave approximately 18" to 316"  
clearance between head of screw and wall.  
4. Hang power unit onto mounting bolts. Make sure top keyhole  
slot and lower slot in mounting bracket are engaged behind  
mounting screws. Pull down to secure.  
“D”  
INTAKE  
5. Remove dirt canister from power unit.  
TOP VIEW  
6. Install soil bag and securely replace dirt canister.  
NOTE: Cyclonic model does not use a soil bag.  
12" MINIMUM TO CEILING  
FRONT VIEW  
TUBING CONNECTIONS  
1. Using rubber couplings and hose clamps, connect intake and  
exhaust tubing to the power unit.  
INTAKE  
2. Connect intake tubing to lower intake tube on power unit.  
3. Connect exhaust tubing to upper exhaust tube on the power unit.  
4. Make sure all tubing connections are air tight.  
5. The exhaust should not be vented into a wall, a ceiling or a  
concealed space in the house. The exhaust line should be  
terminated outside the home, using Model 393 Wall Cap or a  
roof vent.  
“B” TOP  
MOUNT  
BOLT  
EXHAUST  
“C”  
“A”  
OVERALL  
HEIGHT  
WIRING See Figure 20.  
Grounding Instructions – This appliance must be grounded. If  
it should malfunction or breakdown, grounding provides a path of  
least resistance for electric current to reduce the risk of electric  
shock. This appliance is equipped with a cord having an  
equipment-grounding conductor and grounding plug. The plug  
must be plugged into an appropriate outlet that is properly installed  
and grounded in accordance with all local codes and ordinances.  
Danger – Improper connection of the equipment-grounding  
conductor can result in a risk of electric shock. Check with a  
qualified electrician or service person if you are in doubt as whether  
the outlet is properly grounded. Do not modify the plug provided  
with the appliance – if it will not fit the outlet, have a proper outlet  
installed by a qualified electrician.  
This appliance is for use on a nominal 120-volt circuit and has a  
grounding plug. Make sure that the appliance is connected to an  
outlet having the same configuration as the plug. No adapter  
should be used with this appliance.  
1. Connect low voltage wire (18 gauge, 2-conductor, Model 376) to  
two low voltage wires located on outside of the power unit.  
2. The power unit is equipped with a six foot grounded cord. Plug  
cord into 120 volt grounded receptacle.  
18" MINIMUM  
ABOVE FLOOR  
FIGURE 18  
DIMENSIONAL CHART  
MODEL  
DIMENSION  
CV-352  
27"  
A
B
C
D
734  
612  
"
"
"
1358  
TOP OF POWER UNIT  
TOP  
KEYHOLE SLOT  
NOTE: POWER UNIT  
WIRING  
CONTROL LEADS ARE  
TO BE CONNECTED TO  
INLET LEADS WITH  
SUITABLE WIRE  
POWER UNIT  
CONTROL LEADS  
CONNECTORS.  
POWER CORD  
111/2"  
POWER  
UNIT  
120vAC ELECTRICAL  
OUTLET  
INLET  
LEADS  
MODEL 376 (18/2) WIRE  
TO  
OTHER  
INLETS  
LOWER  
SLOT  
MOUNTING  
BRACKET  
FIGURE 19  
FIGURE 20  
INLET  
INLET  
INLET  
7